18 Configuration Guides—XT-9100 Configuration Guide
The source of the analog output signal is defined in the DX-9100
Controller.
Via the GX Tool
Select XTn, AOn, Data, and the “Source Point” field. Enter * and select
the required source variable.
Via the SX Tool
Refer to the Extension Module Configuration section of the DX-9100
Configuration Guide (LIT-6364030).
1. When the XT-9100 is connected to a DX-9100 Controller, you can
view and override the AO value from the DX-9100 front panel. See
Display Panel and Keypads in the DX-9100 Extended Digital
Controller Technical Bulletin (LIT-6364020).
2. The analog output values can be read in percent at Item AOn
(RI.20-27) with the SX Tool.
AO: Source
(with DX-9100
Only)
AO Notes